AWG Wire Gauge Chart

Look up any American Wire Gauge size from 4/0 to 40 — diameter, cross-section and copper resistance, calculated from the AWG formula — or find the nearest gauge for a metric size in mm².

AWG Wire Gauge Chart

AWG to size

4/0 to 40 — e.g. 12, 1/0 or 0000
12 AWG
Example — type your own gauge
Diameter
2.0525 mm · 0.080808 in
Area
3.3088 mm² · 6.5299 kcmil
Resistance at 20 °C
5.2108 Ω/km · 1.5883 Ω/1000 ft

Working

  1. n = 12
  2. Diameter: d = 0.127 mm × 92^((36 − 12) ÷ 39) = 0.127 × 92^0.61538 = 0.127 × 16.162 = 2.0525 mm
  3. In inches: 2.0525 mm ÷ 25.4 = 0.080808 in (80.808 mil)
  4. Area: A = π ÷ 4 × d² = 0.785398 × 2.0525² = 3.3088 mm²
  5. In circular mils: d(mil)² = 80.808² = 6,529.9 cmil = 6.5299 kcmil
  6. Resistance: R = ρ ÷ A = 0.0172414 Ω·mm²/m ÷ 3.3088 mm² = 0.0052108 Ω/m = 5.2108 Ω/km
  7. Per 1000 ft: 5.2108 Ω/km × 0.3048 = 1.5883 Ω/1000 ft

mm² to nearest AWG

mm²
0.005010 to 107.2 mm²
13 AWG
Nearest gauge to 2.5 mm²: 13 AWG is 2.624 mm² (exact index 13.21) — example

13 AWG is also the smallest gauge with at least 2.5 mm².

Working

  1. Diameter of a round conductor with that area: d = √(4 × A ÷ π) = √(4 × 2.5 ÷ π) = 1.7841 mm
  2. Gauge index: n = 36 − 39 × log(d ÷ 0.127) ÷ log(92) = 36 − 39 × log(14.048) ÷ log(92) = 13.21
  3. Nearest gauge: 13.21 rounds to 13 AWG (2.624 mm²)
  4. Smallest gauge with at least 2.5 mm²: 13 AWG (2.624 mm²)

AWG chart: 4/0 to 40

Solid round conductors; resistance for annealed copper at 20 °C. Scroll inside the chart to see every size.

AWG Diameter
mm
Diameter
in
Area
mm²
Area
kcmil
Resistance
Ω/km
Resistance
Ω/1000 ft
4/0 (0000)11.680.4600107.2211.60.16080.04901
3/0 (000)10.400.409685.03167.80.20280.06180
2/0 (00)9.2660.364867.43133.10.25570.07793
1/0 (0)8.2510.324953.48105.50.32240.09827
17.3480.289342.4183.690.40660.1239
26.5440.257633.6366.370.51270.1563
35.8270.229426.6752.630.64650.1970
45.1890.204321.1541.740.81520.2485
54.6210.181916.7733.101.0280.3133
64.1150.162013.3026.251.2960.3951
73.6650.144310.5520.821.6340.4982
83.2640.12858.36616.512.0610.6282
92.9060.11446.63413.092.5990.7921
102.5880.10195.26110.383.2770.9989
112.3050.090744.1728.2344.1321.260
122.0530.080813.3096.5305.2111.588
131.8280.071962.6245.1786.5712.003
141.6280.064082.0814.1078.2862.525
151.4500.057071.6503.25710.453.184
161.2910.050821.3092.58313.174.016
171.1500.045261.0382.04816.615.064
181.0240.040300.82301.62420.956.385
190.91160.035890.65271.28826.428.051
200.81180.031960.51761.02233.3110.15
210.72290.028460.41050.810142.0012.80
220.64380.025350.32550.642452.9616.14
230.57330.022570.25820.509566.7920.36
240.51060.020100.20470.404084.2225.67
250.45470.017900.16240.3204106.232.37
260.40490.015940.12880.2541133.940.81
270.36060.014200.10210.2015168.951.47
280.32110.012640.080980.1598212.964.90
290.28590.011260.064220.1267268.581.84
300.25460.010030.050930.1005338.6103.2
310.22680.0089280.040390.07970426.9130.1
320.20190.0079500.032030.06321538.3164.1
330.17980.0070800.025400.05013678.8206.9
340.16010.0063050.020140.03975856.0260.9
350.14260.0056150.015970.031521,079329.0
360.12700.0050000.012670.025001,361414.8
370.11310.0044530.010050.019831,716523.1
380.10070.0039650.0079670.015722,164659.6
390.089690.0035310.0063180.012472,729831.8
400.079870.0031450.0050100.0098883,4411,049

How to use the AWG chart and calculator

Type a gauge in AWG to size to get its diameter, cross-section area and resistance, with the formulas worked through for that gauge; the matching row in the chart is highlighted. Sizes above 1 AWG can be typed as 1/0 to 4/0 or as 0 to 0000. To go the other way, type a metric conductor size in mm² to nearest AWG: you get the gauge closest on the AWG scale and the smallest gauge that is at least as large. The page address keeps both inputs, so you can bookmark or share a lookup.

The AWG formula

American Wire Gauge is defined by two fixed points — 36 AWG is exactly 0.005 in (0.127 mm) and 4/0 is exactly 0.46 in — with 39 equal ratio steps between them (4/0 counts as n = −3, so 36 − (−3) = 39). That gives:

d(mm) = 0.127 × 92^((36 − n) ÷ 39) A = π ÷ 4 × d² R = ρ ÷ A, with ρ = 1/58 Ω·mm²/m = 0.0172414 Ω·mm²/m

The resistivity is the International Annealed Copper Standard (100% IACS) value at 20 °C, the reference used by the NIST copper wire tables. Area in circular mils is simply the diameter in thousandths of an inch, squared; a kcmil is 1,000 circular mils. Every value in the chart is calculated from these formulas rather than copied from a printed table, and agrees with the published NIST values to within rounding.

Three rules of thumb fall out of the ratio of 92^(1/39) ≈ 1.123 per gauge:

  • 6 gauges smaller halves the diameter (92^(6/39) ≈ 2.005): 10 AWG is 2.588 mm, 16 AWG is 1.291 mm.
  • 3 gauges smaller halves the area and doubles the resistance: 10 AWG is 3.277 Ω/km, 13 AWG is 6.571 Ω/km.
  • 10 gauges smaller is about one-tenth of the area: 1/0 AWG is 53.48 mm², 10 AWG is 5.261 mm².

Worked example: 12 AWG

  1. Diameter: d = 0.127 mm × 92^((36 − 12) ÷ 39) = 0.127 × 92^0.61538 = 0.127 × 16.162 = 2.0525 mm (0.080808 in, or 80.808 mil).
  2. Area: A = π ÷ 4 × 2.0525² = 3.3088 mm², or 80.808² = 6,529.9 circular mils = 6.5299 kcmil.
  3. Resistance: R = 0.0172414 ÷ 3.3088 = 0.0052108 Ω/m = 5.2108 Ω/km, and 5.2108 × 0.3048 = 1.5883 Ω per 1,000 ft.

That resistance is what you need for a voltage-drop estimate. A 20 m cable run has 40 m of conductor (out and back), so R = 0.04 km × 5.2108 Ω/km = 0.20843 Ω. At 10 A, Ohm’s law gives a drop of 10 × 0.20843 = 2.0843 V — try other currents in the Ohm’s law calculator. Real cable runs warmer than 20 °C, which raises the resistance (see below).

Metric sizes and their nearest AWG

Most of the world sizes conductors by cross-section in mm², using the standard series in IEC 60228. The two systems don’t line up, so “equivalent” gauges are approximations. Calculated with the tool above:

Metric size Exact AWG index Nearest AWG Smallest AWG with at least that area
0.5 mm² 20.1 20 AWG (0.5176 mm²) 20 AWG (0.5176 mm²)
0.75 mm² 18.4 18 AWG (0.8230 mm²) 18 AWG (0.8230 mm²)
1 mm² 17.2 17 AWG (1.038 mm²) 17 AWG (1.038 mm²)
1.5 mm² 15.4 15 AWG (1.650 mm²) 15 AWG (1.650 mm²)
2.5 mm² 13.2 13 AWG (2.624 mm²) 13 AWG (2.624 mm²)
4 mm² 11.2 11 AWG (4.172 mm²) 11 AWG (4.172 mm²)
6 mm² 9.43 9 AWG (6.634 mm²) 9 AWG (6.634 mm²)
10 mm² 7.23 7 AWG (10.55 mm²) 7 AWG (10.55 mm²)
16 mm² 5.2 5 AWG (16.77 mm²) 5 AWG (16.77 mm²)
25 mm² 3.28 3 AWG (26.67 mm²) 3 AWG (26.67 mm²)
35 mm² 1.83 2 AWG (33.63 mm²) 1 AWG (42.41 mm²)
50 mm² 0.29 1/0 AWG (53.48 mm²) 1/0 AWG (53.48 mm²)
70 mm² −1.16 2/0 AWG (67.43 mm²) 3/0 AWG (85.03 mm²)
95 mm² −2.48 3/0 AWG (85.03 mm²) 4/0 AWG (107.2 mm²)

IEC 60228 conductors are specified mainly by their maximum resistance rather than an exact geometry, so a real “2.5 mm²” conductor may contain slightly less copper than its name suggests. Treat this table as a guide to physical size, not as permission to substitute one cable for another.

Why there are no ampacity numbers here

Many wire charts print a single “max amps” figure next to each gauge. We don’t, because no single figure is correct. The current a cable may carry depends on the insulation’s temperature rating (for example 60 °C, 75 °C or 90 °C), the installation method (in conduit, in a wall with thermal insulation, clipped direct, buried or in free air), the ambient temperature, how many current-carrying conductors are grouped together, the rating of the terminals, and the voltage drop you can accept over the length of the run. Each wiring code turns those factors into its own tables and corrections: the NEC (NFPA 70) in the United States, IEC 60364-5-52 internationally, and national versions such as BS 7671 in the UK. Use the one that applies where you live, and have mains work done or checked by a licensed electrician.

Limits of the chart

  • Temperature. Copper’s resistance rises by about 0.393% per °C near room temperature (the IACS coefficient, 0.00393 per °C at 20 °C). At 60 °C a conductor’s resistance is roughly 16% higher than the chart value.
  • Stranded wire. Stranded conductors of the same gauge have slightly higher resistance per unit length, because the strands spiral and are a little longer than the cable.
  • Other metals. Aluminum conductors have about 61% of copper’s conductivity, so their resistance is about 1.64 times the copper figure for the same gauge.

For converting the diameters, see millimeters to inches; for the running cost of the equipment on the end of the cable, the electricity cost calculator. More tools are in the electricity section.

Frequently asked questions

Why does a bigger AWG number mean a thinner wire?

The gauge number comes from wire drawing: wire was made thinner by pulling it through a series of smaller and smaller dies, and the gauge roughly counted those steps. More draws gave a higher number and a thinner wire. The modern standard keeps the numbering but defines every size by formula, from 4/0 (0.46 in) down to 36 AWG (0.005 in) and beyond.

What is 12 AWG in mm²?

12 AWG has a diameter of 2.053 mm and a cross-section of 3.309 mm² (6.530 kcmil). Its resistance as solid annealed copper at 20 °C is 5.211 Ω/km, or 1.588 Ω per 1,000 ft.

Is 2.5 mm² cable the same as 14 AWG?

No. 14 AWG is 2.08 mm², smaller than 2.5 mm², and 12 AWG is 3.31 mm², larger. The closest size by the formula is 13 AWG (2.62 mm²), which is rarely used for building wire. A size match by area does not make cables interchangeable: what a cable is allowed to carry is set by your wiring code, not by its cross-section alone.

How many amps can 12 AWG wire carry?

This page deliberately gives no current ratings. The permitted current (ampacity) depends on the insulation’s temperature rating, how the cable is installed, the surrounding temperature, how many cables are grouped together and the terminals it connects to. Use the ampacity tables and correction factors in the code that applies to you — the NEC (NFPA 70) in the US, IEC 60364-5-52 or its national version elsewhere — or ask a licensed electrician.

What do 1/0, 2/0, 3/0 and 4/0 mean?

They are the sizes larger than 1 AWG, read as “one aught” to “four aught” and also written 0, 00, 000 and 0000. In the formula they count as n = 0, −1, −2 and −3. 4/0 is exactly 0.46 in (11.68 mm); sizes larger than that are specified directly in kcmil (thousands of circular mils), such as 250 kcmil.

Sources

Last reviewed · Built and checked by the Reeliy team · How we test our tools